How to Make Two-Prong Outlets Safer

Updated: Jun. 07, 2023

Protect against deadly shocks in four easy steps.

testing an outletFamily Handyman

Increase the safety of your old two-prong outlets by installing a new ground fault circuit interrupter receptacle. The GFCI will protect against a deadly shock, even if it’s not connected to a ground. We’ll show you everything you need to install the GFCI yourself.

You might also like: TBD

Time
An hour or less
Complexity
Beginner
Cost
Less than $20

Overview of GFCIs

You can increase the safety of your old two-prong outlets by installing a new ground fault circuit interrupter receptacle. But just because the GFCI has a hole for a third prong, don’t assume you can plug in three-prong plugs. The National Electrical Code (NEC) states that any appliance equipped with a three-prong plug is required to be grounded, and the installation shown does not provide the necessary equipment ground. Also, some computer equipment won’t work properly if it’s not grounded. The outlet will still be ungrounded, but the GFCI will “trip,” cutting off the current and protecting you from electrocution.

Before you start, make sure the outlet box is large enough to safely hold all of the wires and the new receptacle. Here’s the formula to figure the minimum box size required by the NEC: Add 1 for each hot and neutral wire entering the box, 1 for all of the wire clamps, and 2 for each receptacle. (You’d also add 1 if you had any ground wires.) Multiply this figure by 2 for 14-gauge wire and 2.25 for 12-gauge wire to get the minimum box volume in cubic inches. Our standard metal outlet box is defined by the NEC as having 14 cu. in. Consult the code or call your electrical inspector for the volume of your metal box. Plastic boxes have the volume stamped in them.

Test before you start

Make sure the power is off

Turn off the power to the receptacle at the main electrical panel. Then carefully unscrew the outlet and pull it out of the box. Use a simple neon circuit tester to double-check that the power is off. Place the tester leads across both sets of hot and neutral terminal screws. If the tester lights up, shut off other circuits at the main panel until you find the right one.

Before doing any electrical wiring be sure the power is off to the box or wires you’ll be working with.

Remove the old receptacle

Install new “pigtails”

Disconnect the wires from the old receptacle and straighten the bent ends. Cut 6-in. “pigtails” of white and black wires and strip 5/8 in. of insulation from both ends.

Match the gauge of these wires to the amperage of the circuit: 14-gauge for 15-amp circuits and 12-gauge for 20-amp circuits. The correct amperage will be marked on the fuse or circuit breaker whose circuit you’re connecting to. Splice the new white wire to the existing neutral white wires, and the black to the existing hot wires. Make sure the wire connectors you’re using can safely connect the three 14- or 12-gauge wires. This information is printed on the package.

Connect the new GFCI

Make the right connections

Connect the new wires to the GFCI terminals marked “Line.” Connect the black wire to the brass screw and the white wire to the side that’s labeled “white,” “W” or has a silver screw. Do not connect wires to the “Load” terminals. If there’s no equipment ground wire available (copper that’s bare or is covered with green insulation), don’t connect anything to the GFCI ground terminal (green screw).

Screw the receptacle to the box

Fold the wires neatly into the box. Screw the GFCI to the box and install the cover plate. If you didn’t have an equipment ground wire, attach a sticker to the cover plate saying “No Equipment Ground.” This sticker is included with most GFCI receptacles.

Testing your GFCI

Push the test button on your GFCI. The power from the receptacle will be stopped. Press reset to restore power from the GFCI.

GFCI receptacles have two sets of hot and neutral terminals, labeled “Line” and “Load.” The “Line” terminals are for incoming power. Connect the hot and neutral wires from the main panel to these “Line” terminals.

The “Load” terminals are for protecting additional receptacles with the GFCI. Don’t use them unless you know where the wiring goes and whether or not you want to protect those receptacles. The “Load” terminals on our GFCI are covered with yellow tape to prevent someone from inadvertently connecting the power leads to them.

CAUTION!

Aluminum wiring requires special handling. If you have aluminum wiring, call in a licensed pro who’s certified to work with it. This wiring is dull gray, not the dull orange that’s characteristic of copper.

Required Tools for this Project

Have the necessary tools for this DIY project lined up before you start—you’ll save time and frustration.

  • 4-in-1 screwdriver
  • Electrical tape
  • Safety glasses
  • Voltage tester
  • Wire stripper/cutter